| Vin = 24 V Vout = 20 V Viso = 32 kV Pmax = 80 W APPLICATIONS - Auxiliary power supply for high voltage power semiconductors (IGCT,GTO,IGBT) - Measurement and diagnosis equipment in the medium voltage grid - Serially connected high voltage power semiconductors | |
| PARAMETER | TEST CONDITIONS | MIN | TYP | MAX | UNIT |
| Input Voltage Vin | DC voltage | 22 | 24 | 28 | V |
| Output Voltage Vout | DC voltage | 23,2 | 24 | 24,8 | V |
| Max. Output Power Pmax | Vin >= 24V |
| 80 |
| W |
| Input Power | Pout = 80 W, Vin = 24V |
| 90 | 96 | W |
| Insulation Voltage output to ground Viso | 50 Hz AC voltage, 1 min, without Partial Discharge (< 2pC) | 32 |
|
| kV |
| Insulation Capacitance | output to ground |
| 30 |
| pF |
| Max. dv/dt (Insulation) | ground connection at base plate |
|
| 25 | kV/µs |
| Short Circuit Time | output shortened | 60 |
|
| s |
| Length Input Line | 2,0 m |
| Length Output Line | 0,5 m |
| Colours Input Connection | brown = input voltage + blue = input voltage - green / yellow = ground |
| Colours Output Connection | red = output voltage + black = output voltage - |
INSTALLATION INSTRUCTIONS It is important to make a low inductive ground connection. The output lines are not insulated for high voltage. Therefore they must be mounted insulated with a minimum distance of 30 mm to other metallic surfaces. Keep the output lines as short as possible. Due to electrical fields the body of the power supply must have a free distance of 20 mm around. If several power supplies are mounted, a grid of 110 mm is recommended. | DIMENSIONS![]() |
| PARAMETER | TYP | UNIT |
| Height | 135 | mm |
| Weight | 1750 | g |
IMPORTANT NOTICE ALL DATAS ARE PRELIMINARY Siebel & Scholl GmbH reserves the right to change specifications without notice. Siebel & Scholl GmbH makes no warranty regarding the suitability of this product for any particular purpose. Mounting only by technical experts.