- About company
- |
- Products
- |
- News
- |
- Applications
- |
- Contacts
| Vin = 48 V Vout = 30 V AC Viso = 10 kV Pout = 100 W APPLICATIONS - Auxiliary power supply for high voltage power semiconductors (IGCT,GTO,IGBT) - Measurement and diagnosis equipment in the medium voltage grid | |
| PARAMETER | TEST CONDITIONS | MIN | TYP | MAX | UNIT |
| Input Voltage Vin | DC voltage | 40 | 48 | 52 | V |
| Output Voltage Vout | Vin = 48V, AC voltage with rectifier load | 25 | 30 | 39 | V |
| Max. Output Power Pmax | Vin = 48V |
| 100 |
| W |
| Input Power | Pout = 100 W, Vin = 48V |
| 115 |
| W |
| Insulation Voltage output to ground Viso | 50 Hz AC voltage, 1 min, without Partial Discharge (< 10pC) | 10 |
|
| kV |
| Insulation Capacitance | output to ground |
| 30 |
| pF |
| Max. dv/dt (Insulation) | ground connection at base plate |
|
| 25 | kV/µs |
| Short Circuit Time | output shortened | 10 |
|
| s |
| Length Input Line | 1,0 m |
| Length Output Line | 0,5 m |
| Colours Input Connection | brown = input voltage + blue = input voltage - green / yellow = ground |
| Colours Output Connection | red = output voltage ~ |
INSTALLATION INSTRUCTIONS It is important to make a low inductive ground connection. The output lines are not insulated for high voltage. Therefore they must be mounted insulated with a minimum distance of 30 mm to other metallic surfaces. Keep the output lines as short as possible. Due to electrical fields the body of the power supply must have a free distance of 20 mm around. If several power supplies are mounted, a grid of 110 mm is recommended. | DIMENSIONS![]() |
| PARAMETER | TYP | UNIT |
| Height | 135 | mm |
| Weight | 1750 | g |
IMPORTANT NOTICE ALL DATAS ARE PRELIMINARY Siebel & Scholl GmbH reserves the right to change specifications without notice. Siebel & Scholl GmbH makes no warranty regarding the suitability of this product for any particular purpose. Mounting only by technical experts.