FMCC EUROPE
Components and technical solutions for power electronics

ES100 / ES300 / ES500

 Utilisation

Sensors to measure d.c., a.c. or pulsating currents with a galvanic insulation between primary and secondary circuits.
 

Technical data

Molex HE14 connector ES100C ES300C ES500C ES500-9672
JST connector -ES300S ES500S ES500-9673
CablesES100F ES300F ES500F ES500-9674
Nominal primary current  A r.m.s.100 300 500 500                 
Measuring range @ ±15V (±5%) A peak±150 ±500 ±800 ±800
Measuring range @ ±24V (±5%) А peak ±150 ±500 ±800 ±800
Not measurable overload10мс/ч А peak 300 мс/ч 3000 5000 5000
Max. measuring resistance@ IP max & ±15V (±5%) 48 20 7 13
Max. measuring resistance@ IP max & ±24V (±5%) 105 54 60 56
Max. measuring resistance@ IPN & ±15V (±5%) 10 0 0 0
Max. measuring resistance@ IPN & ±15V (±5%)82 45 0 14
Turn number 
 
1000 2000 5000 4000
Secondary current at Ipn    
mA 100 150 100 125
Accuracy at Ipn @ +25°C % ≤±0.5  ≤±0.5 ≤±0.5≤±0.5
Accuracy at Ipn -5 ... +70°C % ≤±1 ≤±1 ≤±1 ≤±1
Accuracy at Ipn -20 ... +70°C % ≤±2.5 ≤±1.5 ≤±1 ≤±1
Offset current@ +25°C mA ≤±0.4 ≤±0.25 ≤±0.25 ≤±0.25
Linearity  % ≤0.1 ≤0.1 ≤0.1 ≤0.1
Thermal drift coefficient-5 ... +70°C µA/°C  ≤10 ≤15 ≤5 ≤6.25
Thermal drift coefficient-20 ... +70°C µA/°C ≤80 ≤40 ≤16 ≤20
Delay time µs ≤1 ≤1 ≤1 ≤1
di/dt correctly followed  A /  µs  ≤50 ≤50 ≤100 ≤100
Bandwidth-1dB kHz ≤100 ≤100 ≤100 ≤100
Max. no-load consumption current@ ±24V (±5%) mA ≤12 ≤12 ≤12 ≤12
Secondary resistance@ +70°C ≤30 ≤33 ≤76 ≤53
 Dielectric strength Primary/Secondary 50Гц, 1 мин kV3 3 3 3
 Supply voltage±5% V d.c. ±12 ... ±24 ±12 ... ±24 ±12 ... ±24 ±12 ... ±24
Voltage drop ≤2.5 ≤1 ≤1 ≤1
Mass  кг 0.050 0.115 0.210 0.210
Operating temperature°C -20 ...+70 -20 ...+70 -20 ...+70 -20 ...+70
Storage temperature°C -25 ... +85 -25 ... +85 -25 ... +85 -25 ... +85

General data
●   Plastic case and insulating resin are self-extinguishing.
●   Fixing holes in the case moulding for two positions at right angles.
●   Direction of the current: A primary current flowing in the direction of the arrow results in a positive secondary output current from terminal M. 
 Secondary connection
● Molex HE14 connector (ref.: 22-11-10 31)
● JST connector (ref.: B3P-VH)
● 3 x 200 mm cables (cross section 0.38 mm2)
 Primary connection
Hole for primary conductor. The temperature of the primary conductor in contact with the case must not exceed 100°C.